Nat Airconditioning Engineers Private Limited
Comparative Analysis between Domestic Water Heaters & Heat Pump for Residences
| Comparative Analysis between Domestic Water Heaters & Heat Pump for Residences |
| Parameters |
Units |
Systems |
| |
|
Domestic Heater |
Heat Pump |
| No of bathrooms |
No |
100 |
100 |
| Ltrs / bath |
Litres |
30 |
30 |
| Total requirement of hot water to be heated from 20 °C to 50 °C |
lts/day |
3000 |
3000 |
| Energy required for heating( Ltrs x Temp Diff ) |
kCal/day |
90000 |
90000 |
| Energy required in KWH = ( Kcals /860 ) |
KWH |
104.65 |
104.65 |
| Electrical Energy required for heating/day ( for Domestic Heater ) |
KWH/day |
104.65 |
|
| Electrical Energy required for heating/day ( for Heat Pump ) |
KWH/day |
|
44 |
| Cost of energy/kwh |
Rs. |
10 |
10 |
| Cost of operations/day |
Rs. |
1047 |
440 |
| Energy savings/day |
Rs. |
|
607 |
| Energy savings/day |
Rs. |
|
221555 |
| Cost of water heaters,installation @Rs 10,000 each |
100 |
1000000 |
|
| Cost of Heat Pump installation @ Rs 5 lacs( HP)+ Rs 4 lacs (piping and accessories) |
|
|
900000 |
| Difference in cost of installation |
|
|
100000 |
| Nett cost savings in instalation and annual operation |
|
|
321555 |
Nat Airconditioning Engineers Private Limited
Comparative Analysis between Fuel Fired Boiler & Heat Pump
| Comparative Analysis between Fuel Fired Boiler & Heat Pump |
| Parameters |
Units |
Systems |
| |
|
Boiler |
Heat Pump |
| Total requirement of hot water to be heated from 20 °C to 50 °C |
lts/day |
10000 |
10000 |
| Energy required for heating( Ltrs x Temp Diff ) |
kCal/day |
300000 |
300000 |
| Energy required in KWH = ( Kcals /860 ) |
KWH |
|
349 |
| Efficiency of Boiler |
% |
85 |
|
| Specific gravity of Diesel |
|
0.89 |
|
| Calorific value of Diesel |
kCal/kg |
9850 |
|
| Diesel consumption |
Lts/day |
40 |
|
| Rate of Diesel |
Rs./Lts |
75 |
|
| Operational Cost of Fuel fired Boiler per day |
Rs./day |
3000 |
|
| Heat Pump capacity ( 22 KW ) |
kCal/hr |
|
18920 |
| No. of hours of operation of Heat Pump for 10000 lts |
Hours |
|
16.00 |
| Gross connected power |
kW |
|
8 |
| Net power consumtion |
KWH |
|
128.00 |
| Cost Of Power |
Rs./kWh |
|
10 |
| Operational Cost of Heat pump per day (8 x 16 X 8 = Rs. 1024 ) |
Rs./day |
|
1280 |
| Operational Saving per day (3000 - 1280) = Rs 1720 |
Rs./day |
|
1720 |
| Annual operational Saving ( Rs 1720 x 360) |
Rs./Annum |
|
6,19,200 |